Actuator Frequently Asked Questions
1. How do I size a VPVL actuator if
I only have 40 PSI air pressure?
If you have only 40 psi and you would
like to apply a VP-VL spring return
actuator, the most effective spring
combination is three springs on each
piston. This designation is SR3. The
easiest approach is to take standard 60
psi ( SR 4/5 ) unit from stock and
remove one spring from the piston that
has four springs and then remove two
springs from the piston that has five
springs. Having done this you will have
three springs remaining on each piston (
SR3 ). The torque output for SR3
actuators running at 40 psi is in the
table below.
|
|
Air
Stroke |
Spring
Stroke |
|
VPVL05 SR3
|
2 |
3 |
|
VPVL10 SR3
|
4 |
4 |
|
VPVL20 SR3
|
8 |
8 |
|
VPVL25 SR3
|
11 |
12 |
|
VPVL30 SR3
|
18 |
20 |
|
VPVL35 SR3
|
28 |
35 |
|
VPVL40 SR3
|
38 |
43 |
|
VPVL45 SR3
|
64 |
70 |
|
VPVL50 SR3
|
75 |
88 |
|
VPVL60 SR3
|
145 |
165 |
|
VPVL70 SR3
|
350 |
425 |
If you would like further assistance
in actuator sizing, please contact
Summit Controls.
Back to Top
2. What are the power requirements of
Rexa Electraulic actuators?
The power requirements depend on the
power module of the actuator. Here is a
list of modules and their power
requirements:
- Single B-pump Power Module: 120
VAC, 4 amp
- Single C-pump Power Module: 120
VAC, 8.5 amp
- Dual C-pump Power Module: 120
VAC, 15 amp
- Single 1/4D-pump Power Module:
120 VAC, 10 amp
- Single 1/2D-pump Power Module:
120 VAC, 10 amp
- Single D-pump Power Module: 240
VAC, 10 amp
- Dual D-pump power Module: 240
VAC, 20 amp
Ball Valve Frequently Asked
Questions (FAQ)
1. What is a full bore valve?
A full bore (or full port) valve is
one where the hole in the ball is equal
in diameter to the hole in the pipe. In
other words, if you were to look down a
piece of pipe which also contained the
valve, you would not notice any
constriction at the location of the
valve.
Back to Top
2. What is a reduced bore valve?
A reduced bore ( also called a
standard bore or port) valve is one
where the hole through the ball is
smaller than the hole in the pipe. In
some valves such as the Jamesbury 5000
series, there is a gradual narrowing so
that the valve almost looks like a vena
contracta. In other valves, such as the
reduced bore Jamesbury 4000 series, the
reduction is simply a shoulder.
Often, the reduction in diameter is
to the next standard size. For example,
a 2" (nominal size) reduced bore valve
would have a 1.5" bore in the ball. A
1.5" (nominal size) reduced bore valve
would have a 1.25" bore in the ball and
so on. This comes from a rule of thumb
which actually coined the term "standard
bore" as much as the desire for modular
design to allow the same ball to be used
in one size of full bore valve and
another of a standard bore. Long time
ago, the engineers noticed that to get
good control, very often the solution
was to use a full bore valve of one size
smaller than the pipe you were using.
Now, this arrangement required reducers
on either end of the valve. Someone then
came up with the idea of integrating the
reducers in to the valve and the
standard bore valve was born.
Back to Top
3. What is the pressure loss
difference between a Full Bore and a
Reduced Bore valve?
Engineers as well as pipe designers
feel that because of the restriction in
a reduced bore ball valve, that a
significant amount of pressure loss
happens. Actually, it is less than one
might think. We will use Neles
Automation's valve sizing program
Nelprof© to demonstrate how little
difference there actually is. The
conditions we will use are as follows:
- Flow rate: 150
gpm
- Upstream Pressure:
50 psig
- Temperature:
75F
We will adjust the differential
pressure until the valve is showing as
close to 100% open as possible. Here is
the sizing of the full bore valve:

Using the same process data, we will
size a reduced bore valve.

The difference is less than a tenth
of a psi. Granted that the reduced bore
valve has a pressure loss that is about
an order of magnitude greater, either
case becomes insignificant when compared
to the pump output. For the savings
available from using the reduced bore
valves, it should be considered.
Back to Top
4. How does the Jamesbury Lip Seal
design work?
Jamesbury's lip seal deisgn uses a
completely different sealing principle
than a typical "Jam" seat. A "jam" seat
is simply jammed between the body and
the ball and uses the compression of
assembly to provide the forces necessary
to create a seal. This results in high
operating torques and thermal expansion
problems.
With Jamesbury's Lip seal design, the
ball is cradled between the two seats
but the seal is created by elastic
(spring-like) movement of the seat's lip
rather than compression of the complete
seat. The movement of the lip is limited
by the heel. Once the ball has moved a
pre-determined amount against the lip
due to pressure or thermal expansion,
the ball then contacts the heel and
significantly reduces any subsequent
movement. The benefits of this design
include cavity relief without a relief
hole or upstream pressure. Also, it
reduces the operating torque
requirements for the valve. Finally, the
design copes much better with thermal
expansion than a typical "jam" seat.
Back to Top
How to Size a
Mag Meter ?
The optimum flow velocity for normal
service should be approximately 10 ft/s
at max flow. Use the following steps to
verify that you have chosen the correct
size:
- For normal service at 10 ft/s,
pick a meter size that will measure
equal to or greater than your
maximum flowrate (
See footnote 1
). Refer to table below.
- For slurries, pick a meter size
that gives one of the following
velocity ranges depending on your
meter type:
- Abrasive Slurry = 3 - 8 ft/s
- Non-abrasive slurry = 9 - 15
ft/s
- To verify the appropriateness of
your selection, calculate the flow
velocity as shown in the following
example:
- Abrasive Slurry
- Process Pipe Size: 3"
- Desired max flow rate: 175
USGPM

From the table, obtain the velocity
at 40 ft/s for 3 " meter (955.6).
v = 7.32 ft/s
A 3" meter is the appropriate selection
since v < 8ft/s
|
Meter
Size (inches)
(
See footnote 2
)
|
v = 1
ft/s (min) |
v = 10
ft/s |
v = 40
ft/s |
|
0.1 |
0.0245 |
0.245 |
0.979 |
|
0.125 |
0.0383 |
0.383 |
1.530 |
|
0.25 |
0.1530 |
1.53 |
6.120 |
|
0.375 |
0.3735 |
3.74 |
14.93 |
|
0.5 |
0.8405 |
8.4 |
33.51 |
|
0.75 |
1.494 |
14.94 |
59.75 |
|
1 |
2.334 |
23.34 |
93.34 |
|
1.25 |
3.824 |
38.24 |
153.0 |
|
1.5 |
5.979 |
59.79 |
239.0 |
|
2 |
9.339 |
93.39 |
373.5 |
|
2.5 |
15.78 |
157.8 |
630.9 |
|
3 |
23.90 |
239.0 |
955.6 |
|
4 |
37.35 |
373.5 |
1493 |
|
5 |
58.38 |
583.8 |
2334 |
|
6 |
84.05 |
840.5 |
3361 |
|
8 |
149.43 |
1494 |
5975 |
|
10 |
233.4 |
2334 |
9334 |
|
12 |
336.2 |
3362 |
13422 |
|
16 |
597.9 |
5979 |
23899 |
|
20 |
933.9 |
9339 |
37345 |
|
24 |
1345 |
13450 |
53781 |
|
28 |
1919 |
19190 |
76760 |
|
32 |
2507 |
25070 |
100272 |
|
36 |
3173 |
31730 |
126904 |
|
Footnotes:
1. Due to the rangeability of magmeter
technology, max flow rates of either
less than or more than 10 ft/s are
acceptable. Magmeters are often sized to
match line size. When selecting a
magmeter, keep in mind that measurement
accuracy begins to deteriorate at
velocities below 1 ft/ s. If you find
that your desired flow rate is close to
1 ft/s, consider using a smaller
flowmeter. When reducing piping,
concentric reductions must be used.
2 Full scale analog output may be set
between 1 and 40 ft/s.
Back to Top
Converters
All Converters have the
following features:
- Microprocessor signal
conditioning for fast and stable
dynamic response
- Display forward and reverse
flowrate and total, including the
net integrated total
- Back-lit LCD display
- Aluminum housing with
polyurethane finish (IFC 010 and IFC
020 have polycarbonate convers)
- Minimum of simultaneous 4-20 mA
analog, pulse and status output
- User-friendly keypad for easy
configuration via menu-driven
display (when converter has display)
- HART smart communications option
(except IFC 010)
- IFC 010 - DC-Powered for Battery
Mobile Operation: Remote or integral
for basic applications, 11-32 VDC,
with display, 0.5% accuracy, 4-20
mA, pulse and status output.
- IFC 020 - HART Smart for General
Applications: Remote, Integral or
rack mount for most applications.
110-220 VAC, with display and HART
or RS485 communications, 0.3%
accuracy, 4-20 mA, pulse and status
output.
- IFC 090 - HART Smart for
Industrial Applications: Remote or
integral universal converter,
handles slurries or pulsating flow,
0.3% accuracy, blind or with
display, HART communications,
general purpoer or FM/CSA Class I,
Div 2; 24 VAC/CDV or 110 - 220 VAC,
4-20 mA, pulse and status output,
ontrol input. May be configured with
various output combinations.
- IFC 110 Remote - HART Smart for
Difficult Noisy Flows: Remote
universal converter, handles
slurries or pulsating flow, 0.3%
accuracy, (0.2% is optional);
displat with HART and RS485
communcations, 24VAC/VDC or 110 -
220 VAC, 4-20 mA, pulse and 4 status
outputs, 2 control inputs. May be
configured with various output
combinations. Upgradeable
electronics.
- IFC 110 PF - Tidalflux
Converter: Remote for Tidalflux,
handles partially filled pipes. 1.0%
accuracy, display with HART
communications and internal level
indication, 110-220 VAC, 4-20 mA,
pulse and 4 status output, 2 control
inputs. May be configured with
various output combinations.
Back to Top
AS-i Link Frequently Asked
Questions
1. What is AS-i Link?
It is a field proven standard for
discrete (On/Off) actuators and sensors
and stands for Actuator Sensor
Interface. Although more complex
netwoeks may be used in this role, AS-i
is optimally suited for this level.
Because of its proven reliability, wide
range of bus interfaces and huge
installed base, it is well accepted
throughout the world at this level.
Proven benefits include: Installation
cost savings of over 35%; dramatic
wiring and I/O space reduction; field
devices easily added or removed; simple
structure allows for easy installation
and operation; ease of comprehending.
Back to Top
2. What are some features of AS-i?
- Ideally suited for on/off batch
process valves and other discrete
applications
- 31 field devices per network
master
- Simple electronics for
economical and robust performance
- Transfer medium unshielded
two-wire cable for both data and
power supply
- Signal transmission has high
tolerance to EMI
- Easy to install providing the
greated cost savings with least
complexity
- Free choice of network topology
allows for optimized wiring network
- Variety of gateways available to
seamlessly tie into high level bus
networks
Back to Top
3. Can you
give some specifications for
AS-i?
|
Topology: |
Linear, Star, Tree or Ring |
|
Number
of field devices: |
Maximum of 31 per master |
|
Addressing: |
By
AS-I Master or Hand Held
Programming device |
|
Cabling:
|
Unsheilded 2-wire for Data and
Power (30VDC up to 8 amps).
Standard round or AS-i flat |
|
Cable
Length: |
100
meters per master or 300 meters
with two repeaters |
|
Transmission Rate: |
167
kbps |
|
Signal
Coding: |
Manchester type with Alternating
Pulse Modulation |
|
Cycle
time: |
5
msec. max. with 31 devices |
|
Data
per Message: |
4 bits bi-directional |
|
Access
Procedure: |
Master/Slave |
|
Error
Detection: |
1
parity bit & signal quality
monitoring |
Back to Top
4. What gateways and interfaces are
currently available?
Currently, Stone-L offers the
following connectivity options:
- Modbus (RS232C, RS422, RS485)
- Modbus+
- Profibus (DP, FMS)
- DeviceNet
- CAN
- Interbus-S
In addtion, an ISA card is available
for your PC to connect as the master for
a group of devices.
Back to Top
What field wiring components
are available to help implement a
fieldbus networking system?
|
Components Available |
Protocol
|
|
AS-i
|
DeviceNet |
Fieldbus
|
Profibus
|
Modbus
|
|
Masters and
Gateways |
YES |
YES |
|
YES |
YES |
|
Power Supplies |
YES |
YES |
YES |
YES |
YES |
|
Input/Output
Modules |
YES |
YES |
YES |
|
YES |
|
Drop Connectors |
YES |
YES |
YES |
YES |
YES |
|
Power
Conditioners and Repeaters
|
YES |
|
YES |
|
|
|
Cabling |
YES |
YES |
YES |
YES |
|
|
Handhelds
|
YES |
|
|
|
|
|
Commissioning
Kits |
YES |
YES |
|
|
YES |
Vortex Shedding Flowmeter
Frquently Asked Questions
1. What applications suit Vortex
Shedding flowmeters?
The vortex shedding meter is best
used for gas and steam, as well as
liquids of low viscosity that do not
contain significant amounts of solids.
In fact, steam is the largest single
application for vortex meters. The
vortex meter can be used in most
applications where dP/orifice meters
have been used.
Back to Top
2. What are the benefits of Vortext
Shedding flowmeters?
- Accuracy: The
vortex meter accuracy is +/- 1% of
measured flow over a wide range of
flows.
- Versatility:
The same meter can be used for
liquid, gas or steam.
- Low Pressure Drop:
The pressure drop is
typically less than for comparable
flows using orifice plates. For
example, for a flow of 150 gpm of
water in a 2" vortex meter, the
pressure drop would be 3.3 psi while
in a 2" line using an orifice plate,
the pressure drop would be 11.2 psi.
- Rangeability:
The meter rangeability is very high,
up to 45:1 is possible.
- Lower Cost: The
installed cost of a vortex meter is
more attractive than a differential
pressure meter system up through to
6" size. The installed cost
considers all the components
required as well as the labour on
site to put them together.
- Ease of Installation
- Higher temperatures
up to 800 F are possible
Back to Top
3. What sizes of vortex meters are
available?
Sizes range from 3/4" to 12". They
are available in flanged and wafer
styles.
Back to Top
4. How does a vortex meter work?
The basic concept is that there is a
flow obstruction, or shedder, that
causes the flow to separate and then
shed swirls or vortexes of flow. The
rate at which the swirls are shed is
directly proportional to the amount of
flow passing the shedder. However, one
should note that at very low densities
flowing slowly there is very little
energy in each vortex swirl. At some
point in the flow range the energy is
too low for the sensor to detect and the
meter goes to zero. For liquids, the
lower limit of the operating range is
determined by the Reynolds number of the
flow. The Reynolds number (Re) is
viscosity dependant and as the viscosity
goes up, the Re goes down. Vortex meters
are linear in output to an Re of 20,000.
Below that, the vortex shedding process
starts becoming less regular until is
becomes so irregular that it is
unreliable. For optimum performance in a
vortex meter, the viscosity of the
liquid should be water-like.
As the flow strikes the shedder
located in the middle of the flow
stream, the flow must separate to go
around the shedder. As it does, it rolls
up in swirls or vortexes on alternating
sides of the shedder. The vortex swirl
hangs on the shedder growing larger
until its volume gets too large at which
point it separates or sheds from the
shedder. At the point of shedding there
is a momentary low pressure, high
velocity on one side and a momentary
high pressure, low velocity on the other
side. The next vortex swirl then forms
on the opposite side and repeats the
process all over again. The vortex
swirls are always shed on opposidte
sides of the shedder, 80 degrees out of
phase with each other. Each vortex swirl
grows to be the same size so you can
determine a K-factor to express the
ratio of swirls to volumetric flow
regardless of what the flowing material
is. Using this K-factor and counting the
number of pulses, you can determine
total flow or volumetric flowrate and
the meter then outputs this information
on a 4-20 mA signal.
Back to Top
|